Model No.: GDVA-404
Production Capacity: 100pcs/month
Delivery Date: 10 business days
Power: Electronic
Function: CT PT Analyzer
Means of Transport: Ocean,Land,Air
Packing: Wooden Case
Usage: Universal Testing Machine
Brand Name: Gold

Tests for Current Transformer
Tests for Voltage Transformer

Introduction:

 

Model GDVA-404

 

Tests for Current Transformer:

 

1) Excitation curve and parameters test

2) Turns ratio test

3) Ratio and phase error test

4) Polarity mark check

5) Coil resistance measurement

6) Secondary loop burden measurement

7) Error line curve test for protection CT

8) Transient CT parameters test

9) CT nameplate guess

10) Saturation hysteresis loop curve measurement

 

Tests for Voltage Transformer:

 

1) Turns ratio test and phase angle error test

2) Polarity test

3) Secondary burden test

4) Coil resistance test

 

Application:

 

1) CT nameplate check

2) CT parameters check in work burden

3) CT transient parameters analysis

4) CT ratio and phase error calibration

5) PT routine test

 

Technical index:

 

1 Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13

2 Power supply: AC220V±10%,50Hz/60Hz±10%

3 Power output: 0.1~180V (AC)

4 Current output: 0.001~5A(RMS)

5 Power output:300VA

6 Maximum knee voltage measurement:45kv

7 Current measurement:

   Range:0~10A (automatically change range in 0.1/0.4/2/10A)

   Error <±0.1%+0.01%FS

8 Voltage measurement:

   Range:0~200 V (automatically change range in 1V/10V/70V/200V)

   Error < ±0.1%+0.01%FS

9 Turns ratio measurement:

   Range :

   1~35000,  1~2000 error<0.05%

   2000~5000 error>0.1%

   5000~35000 error<0.2%

10 Phase measurement: error:±2min,resolution:0.01min

11 Coil resistance measurement:

     Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)

     Error< 0.2%RDG+0.02%FS

     Maximum resolution:0.1mΩ

12 Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree

13 CT Secondary burden:

     Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)

     Error <0.2%RDG+0.02%FS

     Maximum resolution 0.001ohm

14 PT Secondary burden:

     Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)

     Error <0.2%RDG+0.02%FS

     Maximum resolution: 0.1ohm

15 PT ratio measurement:

     Range :1~35000, 1~5000 error<0.2%

     5000~35000 error<0.5%

16 Saved data groups:>1000groups

17 Work condition: Temperature:-10℃~50℃, moist:≤90%


bigPhoto
 Ms. Daisy Tao

Tel: 86-23-62984892
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Related Products

Company Info

Chongqing Gold M&E Equipment Co.,Ltd. [China (Mainland)]


Business Type:Manufacturer
City: Chongqing
Province/State: Chongqing
Country/Region: China (Mainland)

You May Like:

Product (204)